@ -347,16 +347,16 @@ Temperature sensors used in a system, comment to disable
|
|||
Temperature limits
|
||||
```c
|
||||
#define MAGIC 0x66; //change this value if you want to rewrite the T setpoint in EEPROM
|
||||
#define T_SETPOINT 26.0; //This is a predefind target temperature value (start temperature). EEPROM-saved. The value can be changed using 1. Console 2. Changing the "setpoint" on a display 3. Changing this value AND changing "magic number"
|
||||
#define T_SETPOINT 26.0; //This is a predefined target temperature value (start temperature). EEPROM-saved. Ways to change this value: 1. Console command 2. Change the "setpoint" on a display 3. Change value here AND change "magic number" 4. JSON command
|
||||
#define T_SETPOINT_MAX 48.0; //maximum "setpoint" temperature that an ordinary user can set
|
||||
#define T_SETPOINT_MIN 10.0; //min. "setpoint" temperature that an ordinary user can set, lower values are not recommended until antifreeze fluids at hot side are used.
|
||||
#define T_SETPOINT_MIN 10.0; //min. "setpoint" temperature that an ordinary user can set, lower values not recommended until antifreeze fluids at hot side used.
|
||||
#define T_CRANKCASE_MIN 8.0; //compressor (crankcase) min. temperature, HP will not start if T lower
|
||||
#define T_CRANKCASE_MAX 110.0; //compressor (crankcase) max. temperature, overheating protection, HP will stop if T higher
|
||||
#define T_CRANKCASE_HEAT_THRESHOLD 16.0;//crankcase heater threshold: heater will be powered on if T lower
|
||||
#define T_WORKINGOK_CRANKCASE_MIN 25.0;//compressor temperature: additional check. HP will stop if T is lower than this value after 5 minutes of work. Do not set the value too large to ensure normal operation after long pauses.
|
||||
#define T_CRANKCASE_HEAT_THRESHOLD 16.0;//crankcase heater threshold, the compressor heater will be powered on if T lower
|
||||
#define T_WORKINGOK_CRANKCASE_MIN 25.0;//compressor temperature: additional check. HP will stop if T is lower than this value after 5 minutes of work. Do not set the value too high to ensure normal operation after long pauses.
|
||||
#define T_BEFORE_CONDENSER_MAX 108.0; //discharge MAX, system stops if discharge higher
|
||||
#define T_COLDREF_MIN -14.0; //suction min., HP stops if T lower, cold side (glycol) loop freeze protection and compressor protection against liquid
|
||||
#define T_BEFORE_EVAP_WORK_MIN -25.5; //!!!before evaporator (after valve) min. T; can be very low for a few minutes after startup, ex: capillary tube in some conditions; and for all systems: after long shut-off, lack of reagent, 1st starts, and many others
|
||||
#define T_BEFORE_EVAP_WORK_MIN -25.5; //!!!before evaporator (after valve) min. T; can be very low for a few minutes after a startup, ex: capillary tube in some conditions; and for all systems: after long shut-off, lack of refrigerant, 1st starts, and many others
|
||||
#define T_COLD_MIN -15.5; //cold side (glycol) loop freeze protection: HP stops if inlet or outlet temperature lower
|
||||
#define T_HOT_MAX 50.0; //hot loop: HP stops if hot side inlet or outlet temperature higher than this threshold
|
||||
```
|
||||
|
|