## Diagnostic and status messages ## Diagnostic and status messages
**LastStopCause messages. Why system was stopped**<br><br> **LastStopCause messages. Why system was stopped**
| Message | description | | Message | description |
| ------------- | ------------- | | ------------- | ------------- |
| **Normal_stop** | Normal stop, i.e. setpoint sensor temperature > setpoint, so no need to heat anymore | | **Normal_stop** | Normal stop, i.e. setpoint sensor temperature > setpoint, so no need to heat anymore |
@ -147,8 +146,8 @@ qwer
| **E.Tci, E.Tco, E.Tbe, E.Tae, E.Ts1, E.Ts2, E.Tcrc, E.Treg, E.Tac, E.Tbc, E.Tho, E.Thi** | Sensor lost, check wiring. Refer to "T sensors abbreviations"| | **E.Tci, E.Tco, E.Tbe, E.Tae, E.Ts1, E.Ts2, E.Tcrc, E.Treg, E.Tac, E.Tbc, E.Tho, E.Thi** | Sensor lost, check wiring. Refer to "T sensors abbreviations"|
| **E.PresCold** | Cold side pressure too low, check refrigerant charge and pressure sensors | | **E.PresCold** | Cold side pressure too low, check refrigerant charge and pressure sensors |
| **E.PresHot** | Hot side pressure too high, check refrigerant charge and pressure sensors | | **E.PresHot** | Hot side pressure too high, check refrigerant charge and pressure sensors |
<br><br>
**LastStartMessage messages. What event system is waiting for starting work and some additional events**<br><br> **LastStartMessage messages. What event system is waiting for starting work and some additional events**
| Message | description | | Message | description |
| ------------- | ------------- | | ------------- | ------------- |
| **StCntd:_seconds_** | startup countdown, short-term power loss protection | | **StCntd:_seconds_** | startup countdown, short-term power loss protection |