## Diagnostic and status messages
**LastStopCause messages. Why system was stopped**<br><br>
| **Normal_stop** | normal stop, i.e. setpoint sensor temperature > setpoint, so no need to heat anymore<br>
| **P.WtMax:_WATTS_**| Protective stop, overcurrent, double check your system, **MAX_WATTS** and **POWERON_HIGHTIME** options<br>
**E.Tci, E.Tco, E.Tbe, E.Tae, E.Ts1, E.Ts2, E.Tcrc, E.Treg, E.Tac, E.Tbc, E.Tho, E.Thi** Sensor lost, check wiring. Refer to "T sensors abbreviations"<br>
**E.PresCold** Cold side pressure too low, check refrigerant charge and pressure sensors<br>
**E.PresHot** Hot side pressure too high, check refrigerant charge and pressure sensors<br>
**P.Tho** Protective stop, check system, see **T_HOT_MAX** option <br>
**P.Thi** Protective stop, check system, see **T_HOT_MAX** option <br>
**P.Tcrc** Protective stop, check system, see **T_CRANKCASE_MAX** option <br>
**P.Tae** Protective stop, check system, see **T_COLDREF_MIN** option <br>
**P.Tbe** Protective stop, check system, see **T_BEFORE_EVAP_WORK_MIN** option <br>
**P.Tbc** Protective stop, check system, see **T_BEFORE_CONDENSER_MAX** option <br>
**P.Tci** Protective stop, check system, see **T_COLD_MIN** option <br>
**P.Tco** Protective stop, check system, see **T_COLD_MIN** option <br>
P.W.TcrcMIN , see **T_WORKINGOK_CRANKCASE_MIN** option <br>
P.W.wattMIN c_wattage_max/5 , see **MAX_WATTS** option <br>
| Message | description |
| ------------- | ------------- |
| **Normal_stop** | Normal stop, i.e. setpoint sensor temperature > setpoint, so no need to heat anymore |
| **P.WtMax:_WATTS_** | Protective stop, overcurrent, double check your system, **MAX_WATTS** and **POWERON_HIGHTIME** options |
| **E.Tci, E.Tco, E.Tbe, <br> E.Tae, E.Ts1, E.Ts2, <br> E.Tcrc, E.Treg, E.Tac, <br> E.Tbc, E.Tho, E.Thi** | Sensor lost, check wiring. Refer to "T sensors abbreviations"|
| **E.PresCold** | Cold side pressure too low, check refrigerant charge and pressure sensors |
| **E.PresHot** | Hot side pressure too high, check refrigerant charge and pressure sensors |
| **P.Tho** | Protective stop, check system, see **T_HOT_MAX** option |
| **P.Thi** | Protective stop, check system, see **T_HOT_MAX** option |
| **P.Tcrc** | Protective stop, check system, see **T_CRANKCASE_MAX** option |
| **P.Tae** | Protective stop, check system, see **T_COLDREF_MIN** option |
| **P.Tbe** | Protective stop, check system, see **T_BEFORE_EVAP_WORK_MIN** option |
| **P.Tbc** | Protective stop, check system, see **T_BEFORE_CONDENSER_MAX** option |
| **P.Tci** | Protective stop, check system, see **T_COLD_MIN** option |
| **P.Tco** | Protective stop, check system, see **T_COLD_MIN** option |
| **P.W.TcrcMIN** | see **T_WORKINGOK_CRANKCASE_MIN** option |
| **P.W.wattMIN** | c_wattage_max/5 , see **MAX_WATTS** option |
**LastStartMessage messages. What event system is waiting for starting work and some additional events**<br><br>
**StCntd:_seconds_** startup countdown, short-term power loss protection<br>