Update README.md

This commit is contained in:
openhp 2021-03-29 11:22:27 +00:00 committed by GitHub
parent 94b1657f42
commit 4df732e9b8
No known key found for this signature in database
GPG key ID: 4AEE18F83AFDEB23

View file

@ -250,7 +250,6 @@ Other:
| **#Tho>Max** | "Hot out" temperature is too high. See **T_HOT_MAX** option. |
| **#Thi>Max** | "Hot in" temperature is too high. See **T_HOT_MAX** option. |
| **#CaseCold** | Compressor crankcase temperature is too low. The system can't start. This situation occurs on outdoor installations during a winter season and if AC power lost for a few hours. Wait, while the crankcase heater stabilizing your compressor temperature. See **T_CRANKCASE_MIN** option. |
| **#CaseHot** | Compressor is still overheated, waiting. See **T_CRANKCASE_MAX** option. |
| **#Tae<RefMin** | "After evaporator" temperature too low. Preventing cold loop from freezing and protecting suction line from liquid. See **T_COLDREF_MIN** option. |
| **#Tbe<RefMin** | "Before evaporator" temperature too low. Preventing cold loop from freezing. See **T_COLDREF_MIN** option. |