@ -363,15 +363,15 @@ Temperature limits
Watts, cycles times (milliseconds)
```c
#define MAX_WATTS 1000.0 + 70.0 + 80.0 //power limit, watt, HP stops in case of exceeding, example: compressor: ~1000 + hot CP 70 + cold CP 80
#define POWERON_PAUSE 300000 //after power on: wait 5 minutes before the start of HP (protected from power faults)
#define MAX_WATTS 1000.0 + 70.0 + 80.0 //power limit, watt, HP stops if exceeded, example: compressor: ~1000 + hot CP 70 + cold CP 80
#define POWERON_PAUSE 300000 //after power on: wait 5 minutes before starting HP (power faults protection)
#define MINCYCLE_POWEROFF 600000 //after a normal compressor stop: 10 minutes pause (max 99999 seconds)
#define MINCYCLE_POWERON 3600000 //after compressor start: minimum compressor operation time, i.e. work time is not less than this value (or more, depending on the setpoint temperature) 60 minutes = 3.6 KK 120mins = 5.4 kK.
#define POWERON_HIGHTIME 7000 //after compressor start: defines time when power consumption can be 3 times greater than normal, 7 sec. by default
#define COLDCIRCLE_PREPARE 90000 //before compressor start: power on cold CP and wait 90 sec; if false start: CP will off twise this time; and (hotcircle_stop_after - this_value) must be > hotcircle_check_prepare or HP will go sleep cycle instead of start
#define COLDCIRCLE_PREPARE 90000 //before compressor start: power on cold CP and wait 90 sec.; if false start: CP will off twice this time; and (hotcircle_stop_after - this_value) must be > hotcircle_check_prepare or HP will go sleep cycle instead of start
#define DEFFERED_STOP_HOTCIRCLE 1200000 //after compressor stop: wait 20 minutes, if no need to start compressor: stop hot WP; value must be > 0
#define HOTCIRCLE_START_EVERY 2400000 //while pauses: pump on "hot side" starts every 40 minutes (by default) (max 9999 seconds) to circulate water and get exact temperature reading , option used if "warm floor" installation (Thi as setpoint)...
#define HOTCIRCLE_CHECK_PREPARE 300000 //while pauses: ...and wait temperature stabilisation 5 minutes (by default), after that do setpoint checks...
#define HOTCIRCLE_START_EVERY 2400000 //while pauses: pump on "hot side" starts every 40 minutes (by default) (max 9999 seconds) to circulate water and get exact temperature reading, option used if "warm floor" installation (Thi as setpoint)...
#define HOTCIRCLE_CHECK_PREPARE 300000 //while pauses: ...and wait for temperature stabilization 5 minutes (by default), after that do setpoint checks...
#define HOTCIRCLE_STOP_AFTER (HOTCIRCLE_CHECK_PREPARE + COLDCIRCLE_PREPARE + 30000) //...and then stop after few minutes of circulating, if temperature is high and no need to start compressor; value must be check_prepare + coldcircle_prepare + 30 seconds (or more)
```