@ -364,21 +364,21 @@ Temperature limits
Watts, cycles times (milliseconds)
```c
#define MAX_WATTS 1000.0 + 70.0 + 80.0 //power limit, watt, HP stops if exceeded, example: compressor: ~1000 + hot CP 70 + cold CP 80
#define POWERON_PAUSE 300000 //after power on: wait 5 minutes before starting HP (power faults protection)
#define MINCYCLE_POWEROFF 600000 //after a normal compressor stop: 10 minutes pause (max 99999 seconds)
#define POWERON_PAUSE 300000 //after power on: wait 5 minutes before starting HP (power faults protection)
#define MINCYCLE_POWEROFF 600000 //after a normal compressor stop: 10 minutes pause (max 99999 seconds)
#define MINCYCLE_POWERON 3600000 //after compressor start: minimum compressor operation time, i.e. work time is not less than this value (or more, depending on the setpoint temperature) 60 minutes = 3.6 KK 120mins = 5.4 kK.
#define POWERON_HIGHTIME 7000 //after compressor start: defines time when power consumption can be 3 times greater than normal, 7 sec. by default
#define COLDCIRCLE_PREPARE 90000 //before compressor start: power on cold CP and wait 90 sec.; if false start: CP will off twice this time; and (hotcircle_stop_after - this_value) must be > hotcircle_check_prepare or HP will go sleep cycle instead of start
#define DEFFERED_STOP_HOTCIRCLE 1200000 //after compressor stop: wait 20 minutes, if no need to start compressor: stop hot WP; value must be > 0
#define HOTCIRCLE_START_EVERY 2400000 //while pauses: pump on "hot side" starts every 40 minutes (by default) (max 9999 seconds) to circulate water and get exact temperature reading, option used if "warm floor" installation (Thi as setpoint)...
#define HOTCIRCLE_CHECK_PREPARE 300000 //while pauses: ...and wait for temperature stabilization 5 minutes (by default), after that do setpoint checks...
#define HOTCIRCLE_CHECK_PREPARE 150000 //while pauses: ...and wait for temperature stabilization 2.5 minutes (by default), after that do setpoint checks...
#define HOTCIRCLE_STOP_AFTER (HOTCIRCLE_CHECK_PREPARE + COLDCIRCLE_PREPARE + 30000) //...and then stop after few minutes of circulating, if temperature is high and no need to start compressor; value must be check_prepare + coldcircle_prepare + 30 seconds (or more)
```
EEV options
If you are using capillary tube or TXV: simply skip next section
Depending on how many milliseconds are allocated per step, the speed of automatic tuning will change.
Remember that you'll see refrigeration system reaction on every step not immediately, but after few minutes, sometimes after tens of minutes.
EEV options<br>
If you are using capillary tube or TXV: simply skip next section<br>
Depending on how many milliseconds are allocated per step, the speed of automatic tuning will change.<br>
Remember that you'll see refrigeration system reaction on every step not immediately, but after few minutes, sometimes after tens of minutes.<br>
```c
#define EEV_MAXPULSES 250 //max steps, 250 is tested for sanhua 1.3